DC motor CE Certificated Clean Room Hepa Fan Filter Unit ffu with EBM Motor

Short Description:

 1. Our FFU system is very versatile and flexible, capable of
supporting any Clean Room configuration, layout and
level of cleanliness. It can also be used in many other
applications, such as clean booths, clean workbenches,
and Clean Room tunnels.
2. Rustproof aluminium/Self-contain stainless steel / galval
-nium / powder coated steel FF is compact in size and
can be easily installed in Clean Room ceiling grids.
3. Low energy consumption reduces operating cost
4. Our FFU comes with powerful blowers, which is extre-
mely reliable and quiet even under high static pressure.
5. Our FF are capable of achieving Class 10,000 through
Class 1 Clean Room condition.
6. Control for our FFUs can be: 3 speed on device control,
3 speed remote control (with status indicator), computer
control,and main-sub controller system. 


Product Detail

cleanroom technologyHTB1vC9WfbZnBKNjSZFGq6zt3FXaM厂房 1500

DC motor CE Certificated Clean Room Hepa Fan Filter Unit ffu with EBM Motor

◎The FFU group control system can centrally control and monitor a large number of FFUs.
Control FFU operation, stop, speed, and can monitor FFU status and faults.
• The control terminal has a variety of forms such as computers, touch screens, LCD screens, etc. to choose from.
•Support three levels of password protection, distinguish the authority of different operators.
• It can provide on-site layout view to visually display the FFU location and status for easy identification. (LCD screen does not support).
• You can set timed tasks to automatically control the FFU at the specified time (only computer support).
DC motor CE Certificated Clean Room Hepa Fan Filter Unit ffu with EBM Motor

•You can record system logs, and you can view historical operations, equipment failures and other information (only supported by computers).
• Fast communication response speed, the status of 3000 FFUs can be inquired every minute, and the inquiry speed can be doubled by adding a communication interface.
• AC FFU and DC FFU can be mixed in one system, and the group control system provides a unified control interface.
• It can provide dual control functions. When using a computer as the main control terminal, the touch screen or LCD screen can be installed on site as a slave control terminal, 
and the computer and the slave control
All control terminals can monitor and control the FFU.

DC motor CE Certificated Clean Room Hepa Fan Filter Unit ffu with EBM Motor
• The control terminal can be connected with third-party systems such as firefighting and automatic control for data exchange, or control the FFU according to external input signals.
• Sensors such as wind speed and pressure difference can be added to the system, and the data can be displayed and monitored on the control terminal.
• Customized functions can be added according to customer needs.
检测设备
Model FFU0606G/S/A1M-H/U FFU0906G/S/A1M-H/U FFU1206G/S/A1M-H/U FFU1209G/S/A1M-H/U FFU1212G/S/A1M-H/U
Size(mm) AC motor Normal 575×575×320 875×575×320 1175×575×320 1175×875×320 1175×1175×320

Bottom loading

575×575×370 875×575×370 1175×575×370 1175×875×370 1175×1175×320

Face wind speed

H S H S H H H
0.45 0.45 0.45 0.45 0.45

Machine residual external pressure(pa)

50 120 50 120 50 120 50 120 50 120

Standard working condition power consumption(W)

80 150 90 160 110 180 210 220 250 260
Maximum power consumption(W)  DC motor  100 150 150   250   330
Single Noise dB(A) DC motor  48  51  49  52  50  53  53  56  54  57

 HEPA filtration efficiency

99.995%(@0.3µm)    / 99.9995%(@0.12µm)
HEPA SIZE(MM) Normal   570×570×70   870×570×70 1170×570×70 1170×870×70 1170×1170×70
Bottom loading   570×570×110   870×570×110   1170×570×110   1170×870×110   1170×1170×110

Power supply

AC single item,220V/50HV

Way to control

DC        motor 

DC motor FFU, five gears, stepless speed regulation control, group control

Box material

        Galvalume, aluminum, stainless steel(SUS304、SUS430、SUS201)

Note: 1. H is a high static pressure type, S is a standard type; 2. FFUs of the above specifications are not equipped with phase-effect filters, if you need to be equipped with coarse-efficiency filters, you need to add an explanation when ordering, and the height of the FFU is also Will increase by 30mm accordingly.
3 Standard operating conditions refer to the operating conditions when the rated wind speed is 0.45m/s and the residual pressure outside the machine is $0Pa (120Pa). 4. The maximum power consumption is the power consumption when the FFU air volume is at its maximum.

Cleanroom ffu manufacturer

FFU installation site

FFU 1

800


  • Previous:
  • Next: